Fluke 1662 Multifunction Installation Tester delivers solid, basic installation testing features.
The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.
- Measures RCD switching time and tripping level (ramp test)
- Measures trip time and current for RCD type A & AC in one test
- Measures RCD variable current
- Provides automatic RCD test sequence
- Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
- Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
- Includes a phase sequence indicator
- Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead
A solid, reliable, basic installation tester
- Tests voltage and frequency
- Checks wiring polarity to detect broken N wires
- Measures insulation resistance and loop and line resistance
- Measures motor windings with continuity test
- Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)
Specifications:
AC voltage measurement:
- Range: 500 V
- Resolution: 0.1 V
- Accuracy 45 Hz ? 66 Hz: 0.8% + 3
- Input impedance: 360 k?
- Overload protection: 660 V rms
Continuity testing (RLO):
- Range (autoranging): 20 ? / 200 ? / 2000 ?
- Resolution: 0.01 ? / 0.1 ? / 1 ?
- Open Circuit Voltage: >4 V
Insulation resistance measurement (RISO):
- Accuracy of tTest voltage (at rated test current): +10%, -0%
- Test voltage:
- 100 V
- 250 V
- 500 V
- 1000 V
- Insulation resistance range:
- 20 M? / 50 M?
- 20 M? / 100 M?
- 20 M? / 200 M?
- 20 M? / 200 M? / 500 M?
- 20 M? / 200 M? / 1000 M?
- Resolution:
- 0.01 M? / 0.1 M?
- 0.01 M? / 0.1 M?
- 0.01 M? / 0.1 M?
- 0.01 M? / 0.1 M? / 1 M?
- 0.01 M? / 0.1 M? / 1 M?
- Test current:
- 1 mA @ 50 k?
- 1 mA @ 100 k?
- 1 mA @ 250 k?
- 1 mA @ 500 k?
- 1 mA @ 1 M?
Loop and line impedance (ZI):
- Range: 10 ? / 0.001 ? / High current m? mode
- Resolution: 0.01 ? / 0.1 ? / 1 ?
Prospective earth fault current, PSC test:
- Range: 1000 A / 10 kA (50 kA)
- Resolution: 1 A / 0.1 kA
- Computation: Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested:
- RCD Type: A4, AC?, G?, S?
- Notes:
- 1 Responds to AC
- 2 General, no delay
- 3 Time delay
- 4 Responds to pulsed signal
- 5 Responds to smooth DC signal
Tripping speed test (?T):
- Current settings?:
- 10-30-100-300-500-1000 mA ? VAR
- 10-30-100 mA
- Multiplier:
- x ?, x 1
- x 5
- Measurement range:
- RCD Type G: 310 ms, 50 ms
- RCD Type S: 510 ms, 160 ms
- Notes:
- ?1000 mA type AC only
- 700 mA maximum type A in VAR mode
- VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (I?N):
- Current range: 30% to 110% of RCD rated current?
- Step size: 10% of I?N?
- Dwell time:
- Type G - 300 ms/step
- Type S - 500 ms/step
- Measurement accuracy: ?5%
- Specified trip current ranges (EN 61008-1):
- 50% to 100% for Type AC
- 35% to 140% for Type A (>10 mA)
- 35% to 200% for Type A (?10 mA)
- 50% to 200% for Type B
- 25% for Type B
- Notes:
- ?30% to 150% for Type A I?N > 10 mA
- 30% to 210% for Type A I?N = 10 mA
- 20% to 210% for Type B
Phase Sequence Indication:
- Icon: icon phase sequence indicator Phase Sequence indicator is active.
General Specifications:
- Size (L x W x H): 10 x 25 x 12.5 cm
- Weight (incl. batteries): 1.3 Kg
- Battery size, quantity: Type AA, 6 ea.
- Sealing: IP-40
- Safety: Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA ?s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
- Overvoltage: CAT III / 500V; CAT IV 300V
- Performance: EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition
Includes:
- 6x AA (IEC LR6) cell batteries
- C1600 hard carrying case
- Zero adapter
- Heavy duty mains cord
- STD standard test lead set
- C1600 hard carrying case
- Padded carrying and waist strap
- Quick reference guide
- TP165X remote control probe and lead
- User's manual on CD-ROM
| Part No | FLU1662 |
|---|---|
| Barcode | 95969766821 |
| Brand | Fluke |
| Product Length (mm) | 100 |
| Product Width (mm) | 250 |
| Product Height (mm) | 125 |
| Voltage | 1000V |
Tags: Electrical Tools, Testers, Fluke, FLUKE 100-1000V Multifunction Installation Tester w. Memory FLU1662